Overcharging shortens the life of ALL batteries!
It is true that MK GEL batteries are charged at a lower
voltage than most batteries. Our batteries should be
charged to no more than 2.35 volts per cell or 14.1
volts for a 12-volt battery at 68º F. The charging
voltage of a battery varies with temperature so you
should always use a temperature compensating charging
system.
Overcharging any Sealed Valve Regulated battery, GEL
or AGM will shorten battery life for reasons listed
below:
SVR batteries are a “recombinant” battery.
This means that the oxygen gas that is normally produced
on the positive plate in all lead acid batteries recombines
with the hydrogen ions on the negative plate.. The “recombination”
of hydrogen and oxygen produces water, which replaces
the moisture in a battery. The recombination reaction
will preserve most of the water if the battery is charged
at the appropriate rates.
Overcharging a SVR battery will overwhelm the recombination
reaction and cause permanent water loss. In essence
the battery dies of dehydration. The more the battery
is overcharged, the quicker it will dry out. This is
true of all Sealed Valve Regulated Batteries, GEL or
AGM.
Batteries are charged at different voltages for different
temperatures. Batteries are charged at lower voltages
in high temperatures and higher voltages in lower temperatures.
For this reason you want to make sure your temperature
probe is plugged in and functioning correctly.
All of the above being said, a GEL Battery will not
be immediately ruined due to overcharging. Below is
a chart of expected cycle life of our GEL Battery when
charging is done at the recommended voltage and at various
degrees of overcharging. Keep in mind that the recommended
voltage changes with temperature. See the below chart
for the correct voltage/temperature setting. |